C10 cable mounted

1,1 kV Coupler

C10 cable mounted

Design: cable mounted coupler (plug & receptacle)
Contact assignment: 3 phase, 1 ground, 2 pilot contacts
Rated voltage: 600 V, 1 kV 3 AC
Rated withstand voltage: 2 kV (1 min) dry
Rated current: 145 A, 160 A, 225 A, 325 A
Frequency: 50 – 60 Hz
Protection class: IP 65
Ambient temperature: -25 °C to +45 °C
Sealing: EPDM
Cable cross section: max. 25 mm²
Material: sea water resistant aluminum AA 356.2
Surface treatment: nature, epoxy powder coating
Dimensions P / R (L x H): 572 x 164 mm / 457 x 165 mm (for C10D)
Weight Plug / Receptacle: 11,56 kg / 10,66 kg (for C10D)

Further Information for C10 Series

  • The strain relief entrance fittings are included with the C10 coupler series.
  • The entrance fitting gasket kits are normally not included with the C10 coupler series. For Europe, there are exceptions, so this point must be requested on a case by case basis.
  • There is no termination kit required for the C10 coupler series.
  • Potting compound is not neccessary for the safe installation of the C10 coupler series.
Cable diameter Article number
(mm) (in)
20,8 – 22,1 0.82 – 0.87 C150F3004
22,4 – 23,9 0.88 – 0.94 C150F3005
24,1 – 25,7 0.95 – 1.01 C150F3006
25,9 – 26,9 1.02 – 1.06 C150F3007
27,2 – 28,4 1.07 – 1.12 C150F3008
28,7 – 31,8 1.13 – 1.25 C150F3009
32,0 – 34,8 1.26 – 1.37 C150F3010
35,0 – 38,1 1.38 – 1.50 C150F3011
38,4 – 41,1 1.51 – 1.62 C150F3012
41,4 – 44,5 1.63 – 1.75 C150F3013
44,7 – 47,5 1.76 – 1.87 C150F3014
47,8 – 50,8 1.88 – 2.00 C150F3015
Cable diameter Article number
(mm) (in)
51,1 – 53.8 2.01 – 2.12 C150F3016
54,1 – 57,2 2.13 – 2.25 C150F3017
57,4 – 60,2 2.26 – 2.37 C150F3018
60,5 – 63,5 2.38 – 2.50 C150F3019
63,8 – 66,5 2.51 – 2.62 C150F3020
66,8 – 69,9 2.63 – 2.75 C150F3021
70,1 – 72,9 2.76 – 2.87 C150F3022
73,2 – 76,2 2.88 – 3.00 C150F3023
76,5 – 79,2 3.01 – 3.12 C150F3024
79,5 – 82,6 3.13 – 3.25 C150F3025
82,8 – 85,6 3.26 – 3.37 C150F3026
85,9 – 88,9 3.38 – 3.50 C150F3027
Suitable for C80, C150, CEM150 and C250 coupler series
Pay attention: The sealing inserts normally must be ordered separately!