Repair Joints
Cable Joints
LoviSil® Repair Joint
Application: | cable reparation (one and three core) |
Type of cable: | universal use for paper-insulated (PILC, PICAS) and polymeric cables (XLPE, EPR) |
Connection possibilities: | – multi-core cables – small and large cable cross sections – armored and non-armored cables |
Rated voltage: | 12 kV up to 24 kV |
Conductor cross section: | 35 to 400 mm² |
Outer cable diameter: | max. up to 105 mm |
Material enclosure joint: | ABS (red) |
Filling resin installation enclosure: | silicone, liquid (LoviSil®) |
Filling resin joint: | polyurethane (2-component PUR-resin) |
Water pressure test: | 2 bar |
Modular design: 1. module 2. module 3. module |
flexible and universal modular system basis module (hardware components for joint) resin module (Protolin®, LoviSil®) cable module (termination and installation set) |
Certificates: | HD 628, HD 629 (CENELEC), IEC EN 61442, IEEE 404 |
Customized solutions: | on request |
Types of cable joints
Rated Voltage | Type of Joint | Type of Cable | Conductor Cross Section [mm²] |
Conductor Cross Section Crossed Conductor [mm²] |
Max. Outer Cable Diameter [mm] |
---|---|---|---|---|---|
12 kV | M105 | polymeric/paper (3 x 1-core) polymeric/paper (3-core) |
35 – 400 35 – 400 |
not applicable 35 – 300 |
48 105 |
24 kV | M105 | polymeric/paper (3 x 1-core) polymeric/paper (3-core) |
95 – 400 95 – 400 |
not applicable 95 – 150 |
48 105 |