Cross-Bonding Joints

Cable Joints

LoviSil® Cross-Bonding Joint

Application: reduction of cable losses caused by circulating currents
Type of cable: universal use for paper-insulated (PILC, PICAS)
and polymeric cables (XLPE, EPR)
Connection possibilities: – single-core cables
– small and large cable cross sections
– armored and non-armored cables
Rated voltage: 12 kV up to 36 kV
Conductor cross section: 70 to 1000 mm²
Outer cable diameter: max. up to 105 mm
Material enclosure joint: ABS (red)
Filling resin installation enclosure: silicone, liquid (LoviSil®)
Filling resin joint: polyurethane (2-component PUR-resin)
Water pressure test: 2 bar
Modular design:
1. module
2. module
3. module
flexible and universal modular system
basis module (hardware components for joint)
resin module (Protolin®, LoviSil®)
cable module (termination and installation set)
Certificates: HD 628, HD 629 (CENELEC), IEC EN 61442, IEEE 404
Customized solutions: on request

Types of cable joints

Rated Voltage Type of Joint Type of Cable Conductor Cross Section
[mm²]
Conductor Cross Section
Crossed Conductor [mm²]
Max. Outer Cable Diameter
[mm]
12 kV M75 polymeric (1 x core) 95 – 630 not applicable 72
12 kV M85 polymeric (1 x core) 800 – 1000 not applicable 82
24 kV M75 polymeric/paper (1-core) 95 – 240 not applicable 72
24 kV M85 polymeric (1 x core) 300 – 630 not applicable 82
24 kV M105 polymeric (1 x core) 800 – 1000 not applicable 105
36 kV M85 polymeric (1 x core) 70 – 500 not applicable 82
36 kV M105 polymeric (1 x core) 630 – 1000 not applicable 105