Cross-Bonding Joints
Cable Joints
LoviSil® Cross-Bonding Joint
Application: | reduction of cable losses caused by circulating currents |
Type of cable: | universal use for paper-insulated (PILC, PICAS) and polymeric cables (XLPE, EPR) |
Connection possibilities: | – single-core cables – small and large cable cross sections – armored and non-armored cables |
Rated voltage: | 12 kV up to 36 kV |
Conductor cross section: | 70 to 1000 mm² |
Outer cable diameter: | max. up to 105 mm |
Material enclosure joint: | ABS (red) |
Filling resin installation enclosure: | silicone, liquid (LoviSil®) |
Filling resin joint: | polyurethane (2-component PUR-resin) |
Water pressure test: | 2 bar |
Modular design: 1. module 2. module 3. module |
flexible and universal modular system basis module (hardware components for joint) resin module (Protolin®, LoviSil®) cable module (termination and installation set) |
Certificates: | HD 628, HD 629 (CENELEC), IEC EN 61442, IEEE 404 |
Customized solutions: | on request |
Types of cable joints
Rated Voltage | Type of Joint | Type of Cable | Conductor Cross Section [mm²] |
Conductor Cross Section Crossed Conductor [mm²] |
Max. Outer Cable Diameter [mm] |
---|---|---|---|---|---|
12 kV | M75 | polymeric (1 x core) | 95 – 630 | not applicable | 72 |
12 kV | M85 | polymeric (1 x core) | 800 – 1000 | not applicable | 82 |
24 kV | M75 | polymeric/paper (1-core) | 95 – 240 | not applicable | 72 |
24 kV | M85 | polymeric (1 x core) | 300 – 630 | not applicable | 82 |
24 kV | M105 | polymeric (1 x core) | 800 – 1000 | not applicable | 105 |
36 kV | M85 | polymeric (1 x core) | 70 – 500 | not applicable | 82 |
36 kV | M105 | polymeric (1 x core) | 630 – 1000 | not applicable | 105 |